TM 9-2320-365-20-2
2-1351
CONTINUITY TEST
(1) Set multimeter to ohms.
(2) Connect positive (+) probe of multimeter to
110/208 vac IN connector pin C.
(3) Connect negative (-) probe of multimeter to
circuit breaker CB1 right input terminal and
note reading on multimeter.
(4) If continuity is not present, repair or replace
wire 502 (para 2-40).
(5) If continuity is present, troubleshoot 110 vac
power source.
(6) Position circuit breaker CB1 to OFF.
(7) Install cover on 110/208 VAC POWER
DISTRIBUTION PANEL with six screws.
(8) Install dust cover on 110/208 VAC power IN
connector.
(9) Position circuit breaker CB1 to ON.