TM 9-2320-365-20-2
2-1123
CONTINUITY TEST
(1) Remove diffuser from lighting fixture DS81.
(2) Remove tube lock holder from each end of two
fluorescent lamps.
(3) Remove two fluorescent lamps from lighting
fixture DS81.
(4) Set multimeter to ohms.
(5) Connect positive (+) probe of multimeter to
one pin on end of fluorescent lamp.
(6) Connect negative (-) probe of multimeter to
other pin on same end of fluorescent lamp and
note reading on multimeter.
(7) Perform steps (5) and (6) on opposite end of
fluorescent lamp.
(8) If continuity is not present at either end of
fluorescent lamp, replace fluorescent lamp
(para 16-59).
(9) Perform steps (5) through (8) on second
fluorescent lamp.