CONTINUITY TEST
Use care when testing electrical connectors.
Do not damage connector pins or sockets
with multimeter probes. Failure to comply
may result in damage to equipment.
CAUTION
NOTE
Inspect connector pins/sockets for damage,
corrosion, and serviceability. Check that
connector pins are not pushed back and
are capable of making good contact.
TM 9-2320-365-20-1
Change 1 2-667
(1) Remove kick panel (para 16-3).
(2) Disconnect connector clamp from
connector P115.
(3) Disconnect connector P115 from
WTEC III transmission ECU.
(4) Set multimeter to ohms.
(5) Connect positive (+) probe of multimeter
to PDP, where WTEC III relay K25
terminal 85 was removed.
(6) Connect negative (-) probe of multimeter
to connector P115 socket 4 and note
reading on multimeter.
(7) If continuity is not present, repair wire
113 from WTEC III relay K25
terminal 85 to connector P115 socket 4
(para 2-40) or replace WTEC III
dashboard cable assembly (para 7-11).
(8) Connect connector P115 to WTEC III
transmission ECU.
(9) Connect connector clamp to connector P115.