CONTINUITY TEST
(1) Loosen screw in terminal board TB3.
(2) Remove wire 3085W from terminal board
TB3.
(3) Set multimeter to ohms.
(4) Connect positive (+) probe of multimeter to
wire 3085W.
(5) Connect negative (-) probe of multimeter to
ground socket of 110 vac receptacle J233
and note multimeter.
(6) If continuity is not present, repair or replace
wire 3085W (para 2-40).
(7) If continuity is present, repair or replace wire
3085AF (para 2-40).
(8) Install wire 3085W on terminal board TB3.
(9) Tighten screw in terminal board TB3.
(10) Install wire 1499G on terminal board TB4.
(11) Tighten screw in terminal board TB4.
(12) Install cover on 110/208 VAC POWER
DISTRIBUTION PANEL with six screws.
(13) Install cover on 110 vac outlet J233 with
screw.