Change 1 2-1201
TM 9-2320-365-20-2
CONTINUITY TEST
(1) Loosen screw in terminal board TB3.
(2) Remove wire 3085M from terminal board
TB3.
(3) Set multimeter to ohms.
(4) Connect positive (+) probe of multimeter
to wire 3085M.
(5) Connect negative (-) probe of multimeter
to ground socket of 110 VAC receptacle
J231 and note reading on multimeter.
(6) If continuity is not present, repair or
replace wire 3085M (para 2-40).
(7) If continuity is present, repair or replace
wire 3085AB (para 2-40).
(8) Position wire 3085M on terminal board
TB3.
(9) Tighten screw in terminal board TB3.
(10) Position wire 1499C on terminal board
TB4.
(11) Tighten screw in terminal board TB4.
(12) Install cover on 110/208 VAC POWER
DISTRIBUTION PANEL with six screws.
(13) Install cover on 110 VAC outlet J231 with
screw.