TM 9-2320-365-20-2
2-1132
TEST OPTIONS
REASON FOR QUESTION
KNOWN INFO
Continuity Test or
STE/ICE-R #91
YES
NO
8.
POSSIBLE PROBLEMS
Faulty wire 1499J.
Faulty wire 3085C.
If continuity is not present,
wire 1499J is faulty. If
continuity is present, wire
3085C is faulty.
Lighting fixtures DS82
and DS83 OK.
Is continuity present
from wire 1499J in 110/208
VAC POWER DISTRIBUTION
PANEL to wire 1499J in
lighting fixture DS80?
Repair or replace wire 3085C between
110/208 VAC POWER DISTRIBUTION
PANEL and lighting fixture DS80
(para 2-40).
Repair or replace wire 1499J between
110/208 VAC POWER DISTRIBUTION
PANEL and lighting fixture DS80
(para 2-40).
e103. M1079 LIGHTING FIXTURE(S) DS80 AND/OR DS81 DO NOT OPERATE (CONT)