e108. M1079 110 VAC OUTLET J232 DOES NOT OPERATE IN NORMAL MODE (CONT)
TM 9-2320-365-20-2
2-1182 Change 1
4.
KNOWN INFO
TEST OPTIONS
Continuity Test or
STE/ICE-R Test #91
REASON FOR QUESTION
Fluorescent lights OK.
110 VAC outlet J233 OK.
110 VAC receptacle J232 OK.
Wire 1499B OK.
POSSIBLE PROBLEMS
Faulty wire 3085K.
Faulty wire 3085AA.
Is continuity present on
wire 3085K from 110/208
VAC POWER DISTRIBUTION
PANEL to 110 VAC
receptacle J232.
If continuity is not present,
wire 3085K is faulty. If
continuity is present, wire
3085AA is faulty.
Repair or replace wire 3085AA
(para 2-40).
YES
Repair or replace wire 3085K
(para 2-40).
NO